Appendix D: Replacing the Fuses (For Service Personnel Only)
This product contains replaceable fuses. To avoid serious injury and/or damage to your
Avocent PM PDU, make sure:
• The PDU is disconnected from a power source and all connected devices are turned off
before replacing a fuse.
• Fuses are replaced with an Avocent approved branch circuit fuse class G time delay type
with 20A 600 VAC rating.
CAUTION: Avocent recommends using the Avocent fuse replacement kit. Avocent is not responsible for any issues
that may occur using any other vendor’s fuse replacement kit.
• Fuses are replaced by qualified personnel.
• Fuses are denoted with the following markings on the board: FC1-FC2, FC3-FC4, FC5-
FC6, FC7-FC8, FC9-FC10, FC11-FC12, FC13-FC14, FC15-FC16, FC17-FC18, FC19-FC20,
FC21-FC22, FC23-FC24, FC1-FC5, FC2-FC6, FC3-FC7, FC4-FC8 . Refer to Appendix B
for fuse(s) to outlet(s) correlation.
WARNING: There is a risk of explosion if the lithium battery is replaced with an incorrect type. Dispose of used
batteries according to the manufacturer’s instructions.
CAUTION: Double pole/neutral fusing.
108 Avocent PMPDU Installer/User Guide