Avocent PM 3000 Guía de usuario Pagina 82

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 108
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 81
74 Avocent PM PDU Installer/User Guide
PM1009H-401 1084-
799
US single
phase 200-240
VAC 2W + PE
50/60 Hz
NEMA L6-30P
24A 200-240
VA
C
50/60
Hz
12A 16A
(see note 2)
12A 30A
PM1010H-401 1084-
800
EU single
phase 220-2
40
V
AC 2W + PE
50/60 Hz
IEC309
332P6W
32A 220-240
VA
C
50/60
Hz
10A 16A
(see note 3)
16A 40A
PM1011H 1084-
798
Single phase
100-
240 V
AC
2W + PE
50/60 Hz
IEC320-C20
16A 100-240
VA
C
50/60
Hz
10A N/A N/A 20A
PM2007H-401
PM3007H-401
1083-
794
US single
phase 200-2
40
V
AC 2W + PE
50/60 Hz
NEMA L6-30P
24A 200-240
VA
C
50/60
Hz
12A 16A
(see note 2)
12A 30A
PM2008H-401
PM3008H-401
1083-
796
EU single
phase 220-2
40
V
AC 2W + PE
50/60 Hz
IEC309
332P6W
32A 220-240
VA
C
50/60
Hz
10A 16A
(see note 3)
16A 40A
PM2009H
PM3009H
1083-
792
Single phase
100-
240 V
AC
2W + PE
50/60 Hz
IEC320-C20
16A 100-240
VA
C
50/60
Hz
10A N/A N/A 20A
NOTE 1: When on
e bank is at a maximum 16A, the othe
r banks shall not exceed 12A per bank.
NOTE 2: When one bank is at a maximum 16A, the othe
r bank(s) shall not exceed 8A total.
NOTE 3: When one bank is at a maximum 16A, the othe
r bank(s) shall not exceed 16A total.
NOTE 4: When one bank is at a maximum 32A, the othe
r banks shall not exceed 13A per bank.
NOTE 5: When one bank is at a maximum 32A, the othe
r banks shall not exceed 23A per bank.
Table A.1: Avocent PM PDU Specifications (Continued)
Un
it CMN Input Voltage
Input
Current
Output
Voltage
Outlet
Max
Current
Bank Max
Unbalanced
Current
Bank
Max
Balanced
Current
Listed
Branch
Circuit
Protection